DENYO GENERATOR DCA-1100SPM2

Denyo generators: Designed to be totally user-friendly Maintenance made simple All daily maintenace requirements can be performed from one side of the machine. The large doors gives you full acces to the engine. External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance. Large fuel gauge is fitted for […]

Main specifications

Rated output Continuous: 1000 KVA
Rated output Stand by: 1100 KVA
Engine: Mitsubishi S12H-PTA

Highlight features

  • 2 Fuel consumption is based on operation at 75% load
  • 3 Shown unit lengths are with visor (without visor)
  • 4 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source
  • 5 Depending on location and area, output vollage may differ from values listed in catalog.
Description

Denyo generators: Designed to be totally user-friendly

Maintenance made simple

  • All daily maintenace requirements can be performed from one side of the machine. The large doors gives you full acces to the engine.
  • External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance.
  • Large fuel gauge is fitted for simple viewing.
  • For major engine overhauls, the bonnet can be simply unbolted, which allows full access to the engine.

Transportability

  • The new designs of the DCA series range have achieved significant size and weight reductions over proviously producted models, through improvements in coupling techniques and alternator design.
  • The studry weatherproof steel bonnet on a heavy-duty steel skid base allows easy handling by a forklift.
  • The balance point lifting hook (lug) fitted on the roof of each machine facilitates easy transportation using a crane.
  • All models are modular dessigned, so that generators can be stacked, thereby making the best use of your valuable storage area.

Provision of various protective devices and warning lamps

  • A circuit breaker is provided protect the generator form shorting of the load circuit or an overload.
  • An emergency stop device is provided to automatically detect an engine malfunction and shut down the unit, as well as a warning lamp.

Specification

SPECIFICATION

Frequency: 50Hz
Output Rating Continous 1000 KVA Standby 1100
No.of Phases 3-Phase, 4-Wire
Rated Voltage*1 Single Voltage
Power Factor 0.8 (Lagging)
Voltage Regulation % Within ± 0.5
Excitation Brushless, Rotating Exciter (With A.V.R)
Insulation Class F

ENGINE

Maker &Model Mitsubishi SH12-PTA
Output Rating PS/rpm 1210/1500Kw/rpm 890 /1500
No.of Cylinders-Bore x Stroke mm 12-150×175
Piston Displacement L 37.110
Fuel ASTM No.2 Diesel Fuel Equivalent
Fuel Consumption*² L/h 161
Lube Oil Sump Capacity L 200
Coolant Capacity L 210
Battery x Quantity  190H52x4 or 210H52x4
Fuel Tank Capacity 800

UNIT

Dimesions Length: 6510(5900)*³ (mm)Width: 2200 (mm)

Height: 27900 (mm)

Dry Weight: 14180

SOUND LEVEL

7m dB (A) 1500/1800 rpm (min¯¹)*4 77

Services

MAINTENANCE SERVICE

With U-MAC’s quick maintenance service, routine maintenance has never been so convenient and fast. All you need to do is contact and schedule an...

View detail

Other Equipment

Customer Information






Contacts

Email: info@umac.com.vn

 

Customer Information






Contacts

Email: info@umac.com.vn

Customer Information







Contacts

Email: info@umac.com.vn

© UMAC 2018. All Rights Are Reserved DMCA.com Protection Status