DENYO GENERATOR DCA-800SPK

Denyo generators: Designeded to be totally user-friendly Maintenance is made simpler All daily maintenance requirements can be performed from one side of the machine. The large doors gives you full acces to the engine External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance. Large fuel gauge is fitted […]

Main specifications

Rated continuous output 700 KVA
Rated stand-by output: 770 KVA
Engine: Komatsu SA12V140

Highlight features

  • Fuel consumption is based on operation at 75% load
  • Fully appointed control panels for ease of use and monitoring generator performance
  • Provision of various protective devices and warning lamps
  • Maintenance made simpler
  • Noise suppression is achieved using highly effective sound insulating materials
Description

Denyo generators: Designeded to be totally user-friendly

Maintenance is made simpler

  • All daily maintenance requirements can be performed from one side of the machine. The large doors gives you full acces to the engine
  • External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance.
  • Large fuel gauge is fitted for simple viewing
  • For major engine overhaulsm the bonnet can be simply unbolted, which allows full access to the engine.

Transportability

  • The new designs of the DCA series range have achieved significant size and weight reductions over previously produced models, through improvements in coupling techniques and alternator design.
  • The sturdy weatherproof steel bonnet on a heavy-duty steel skid base allows easy handling by a forklift.
  • The balance point lifting hook (lug) fitted on the roof of each machine facilitates easy transportation using a crane.
  • All models are modular designed, so that generators can be stacked, thereby making the best use of your valuable storage area.

Fully appointed control panels for ease of use and monitoring generator performance

  • indicator
  • AC Ammeter
  • Voltmeter
  • Pilot Lamp
  • Panel Light
  • Circuit breaker
  • Panel light switch
  • Voltage regulator
  • Frequency meter
  • Throttle lever
  • preheat Lamp
  • Emergency stop button
  • starter switch
  • Frequency adjust screw
  • Warning lamp (oil pressure)
  • Warning lamp (Water temperature)
  • Fuel level indicator
  • Earth leakage relay
  • Fuel priming pump button
  • Hour meter

Provision of various protective devices and warning lamps

  • A circuit breaker is provided to protect the generator from shorting of the load circuit or an overload.
  • An emergency stop device is provided to automatically detect an engine malfunction and shut down the unit, as well as a warning lamp.

Specification

ALTERNATOR

Frequency: 50Hz
Output Rating Continous 700KVA Standby 770
No.of Phases 3-Phase, 4-Wire
Rated Voltage*1 Dual Voltage
Power Factor 0.8 (Lagging)
Voltage Regulation % Within ± 0.5
Excitation Brushless, Rotating Exciter (With A.V.R)
Insulation Class F

ENGINE

Maker &Model Komatsu SA12V140
Output Rating PS/rpm 834/1500Kw/rpm 613 /1500
No.of Cylinders-Bore x Stroke mm 12-14×165
Piston Displacement L 30.480
Fuel ASTM No.2 Diesel Fuel Equivalent
Fuel Consumption*² L/h 102
Lube Oil Sump Capacity L 151
Coolant Capacity L 170
Battery x Quantity  190H52x2 or 210H52x2
Fuel Tank Capacity 490

UNIT

Dimesions Length: 6110(5500)*³ (mm)

Width: 1950 (mm)

Height: 2500 (mm)

Dry Weight: 11200

SOUND LEVEL

7m dB (A) 1500/1800 rpm (min¯¹)*4 70

Services

MAINTENANCE SERVICE

With U-MAC’s quick maintenance service, routine maintenance has never been so convenient and fast. All you need to do is contact and schedule an...

View detail

Other Equipment

Customer Information






Contacts

Email: info@umac.com.vn

 

Customer Information






Contacts

Email: info@umac.com.vn

Customer Information







Contacts

Email: info@umac.com.vn

© UMAC 2018. All Rights Are Reserved DMCA.com Protection Status
Customer Support 0833 486 586
Contact
error: Content is protected !!